Buffer Tank

In order for a comfort or industrial purpose cooling system to operate properly and efficiently, the total volume of water in the circulation must be above a certain amount.

Specially designed and manufactured to increase water volume in all chilled water applications where additional water volume is needed.

All chilled water applications where system water volume should be increased.

Industrial cooling,

Machine cooling systems.

All process cooling applications requiring precise temperature control

HVAC cooling,

High-rise buildings - housing, office buildings, hotels.
Buildings that require cooling in winter – shopping malls, factories.
All cooling systems that should be separated by a heat exchanger

In order to prevent temperature stratification and provide a homogeneous heat distribution, there are a number of baffle plates within the tank. By this way, the air in the water can easily be separated and discharged from the top of the tank.

Delivered as perfectly insulated to minimize energy loss.

The outer surface is protected against corrosion by double layer anticorrosive.

Ready to be installed in the system, with flanged connections sized according to tank volume.

Having accessory connection ports for air vent valve and discharge valve.

Before delivery, tested under pressure

1,5 times higher than the operating pressure.

Device Type

Structural

Group

                           Capacity

                            Liters

0 D

mm

H

mm

Connection Ports

Empty

Weight

Kg

BF-100/10-V

 

100

500

1050

DN32

1/2”

3/4”

60

BF-300/10-V

I

300

700

1350

DN50

1/2”

3/4”

105

BF-500/10-V

500

850

1450

DN65

1/2”

1”

180

BF-750/10-V

 

750

850

2050

DN80

1/2”

1”

230

BF-1000/10-V

 

1000

950

2110

DN100

3/4”

1 1/4”

310

BF-1500/10-V

 

1500

1150

2000

DN125

3/4”

1 1/2”

480

BF-2000/10-V

 

2000

1250

2350

DN125

3/4”

1 1/2”

580

BF-2500/10-V

 

2500

1400

2350

DN150

3/4”

2”

670

BF-3000/10-V

 

3000

1400

2770

DN150

3/4”

2”

850

BF-4000/10-V

m

4000

1500

3150

DN200

3/4”

2”

1120

BF-5000/10-V

 

5000

1600

3070

DN200

3/4”

2”

1410

 

         

In order for a comfort or industrial purpose cooling system to operate properly and efficiently, the total volume of water in the circulation must be above a certain amount. This amount is determined by the system capacity and the desired control accuracy. If the total water volume of the system is below this amount, the thermal capacity should be increased, by installing a TANPERA-BF Series Buffer Tank to the system.

Important Note: If more than one tank is used in the system, it is advisable to connect these tanks in series rather than in parallel, to ensure good circulation wthout short circuit.

In order for a comfort or industrial purpose cooling system to operate properly and efficiently, the total volume of water in the circulation must be above a certain amount. This amount is determined by the system capacity and the desired control accuracy. If the total water volume of the system is below this amount, the thermal capacity should be increased, by installing a TANPERA-BF Series Buffer Tank to the system.